Insulation | Air, at ambient pressure |
Rated frequency | 16.7 Hz |
Rated voltage (Un) | 15 kV |
Operating voltages | according to EN 50163 |
Rated impulse voltage (UNi) | 125 kV |
Rated power frequency withstand (Ud) | 50 kV |
Rated current (Ir) | up to 2,500 A |
Rated short circuit current (Ik) | up to 40 kA 1 s |
Rated peak withstand current (Ip) | up to 100 kA |
Installation | Indoor |
Installation height | < 1,000 m above sea level |
Height, overall | 2,300 mm |
Depth, rear access not required | 1,550 mm |
Width | 800 mm |
Weight | approx. 850 kg |
Compartment class | LSC2B-PM |
Internal arc classification | IAC AFLR 40 kA 0.3 s |